6. Function Description
6-72
6.7 2nd Function Group (2nd_[][])
2
nd
function group is equivalent to the parameter group which includes the data related to the 2
nd
motor in case
single inverter controls 2 motors. One of the multi-function terminal input P1 ~ P7 (DIO_01 ~ DIO_07) should be set to
“
2nd Func
”
. The setting ranges and usage of the 2
nd
motor parameter is basically the same as those of the 1
st
motor
parameters. If the multi-function terminal input enables the 1
st
motor, the 1
st
motor parameters become valid.
Similiarly, if the multi-function terminal input enables the 2
nd
motor, the 2
nd
motor parameters become valid.
6.7.1 Jump code (2nd_00)
You can move on to the code you want to check using 2nd_00.
(Example) If you want to move on to 2nd_02,
After pressing the [PROG] key, set to02 using [SHIFT/ESC] / [
▲
(Up)] / [
▼
(Down)] keys and then press the [ENT]
key. If the code to jump to is not found, the nearest code number is selected.
You can check the other code using [
▲
(Up)] / [
▼
(Down)] keys.
6.7.2 2nd motor control mode selection (2nd _01)
In the motor control mode, there are
speed
and
torque
control modes based on the vector control. The speed
sensor such as the pulse encoder is required if speed control (
‘
Speed
’
) and torque control (
‘
Torque
’
) is to be used.
Code
No.
LCD display
Function
Setting range
Unit
Factory
setting
2nd_01
2nd Ctl Mode
2
nd
motor control mode
selection
Speed
Torque
Speed
6.7.3 2nd motor speed setting
1) 2nd_02: The 2
nd
motor maximum speed / 2nd_04: The 2
nd
digital speed setting
Code
No.
LCD display
Function
Setting range
Unit
Factory
setting
2nd_02
2nd Max Spd
2
nd
motor maximum speed
400.0 ~ 3600.0
rpm
1800.0
2nd_04
2nd Spd 0
2
nd
motor multi-step speed 0
0.0 ~ 2
nd
_02
rpm
0.0
2nd
▶
2nd Max Spd
02 1800.0 rpm