3. Installation and Wiring
3-3
3.1.6 Secure the installation space enough to protect the inverter
against the overheating.
At least the room that 30 cm from upper and lower of inverter and 20 cm
from left and right of inverter is required for installing more than 30 kW
products.
3.1.7 Special care should be taken in case the inverter is to be installed in
the panel.
In case more than 2 inverters are to be installed or ventilation fan is to be
installed in the panel, make sure that inverter and ventilation fan is properly
installed. If they are poorly installed, it causes the increase of an ambient
temperature and less effective ventilation. Therefore, be sure to keep the
ambient temperature of inverter below the allowable temperature.
3.1.8 Install the inverter tightly not to get loose using proper sized bolt or
screw.
Min. 5 cm
Min. 10 cm
Min. 5cm
SV-iV5
Min. 10 cm