6. Function Description
6-6
1.1) Speed-L / Speed-M / Speed-H / JOG operation
By defining P1 ~ P4 as
“
Speed-L
”
,
“
Speed-M
”
,
“
Speed-H
”
and
“
Jog Speed
”
, the selected references in FUN goup 12 ~
20 (Multi-step speed 0 ~ 7 and Jog speed) become active as speed reference.
(Example)
To define Multi-function input terminals P1, P2, P3 as Speed-L, Speed-M, Speed-H and P4 as Jog Speed;
Code
LCD display
Description
Setting
range
Unit
Set value
DIO_01
P1 define
Multi-function input terminal P1 define
Speed-L
DIO_02
P2 define
Multi-function input terminal P1 define
Speed-M
DIO_03
P3 define
Multi-function input terminal P3 define
Speed-H
DIO _04
P4 define
Multi-function input terminal P4 define
Jog Speed
When multi-step speed 0 (FUN_12: Speed 0) is selected (P1, P2 and P3 are all OFF), speed reference is input by the
method set in Digital setting by keypad (FUN_12: Speed 0) or Analog speed setting of terminal block or setting by
option. If the jog (FUN_20) of P4 is active, inverter operates with jog frequency regardless of other terminal signal
input.
P1
P2
P3
P4
Set Vaule
OFF
OFF
OFF
OFF
Speed referece in accordance with
FUN_02
ON
OFF
OFF
OFF
FUN_13(Speed 1)
OFF
ON
OFF
OFF
FUN_14(Speed 2)
ON
ON
OFF
OFF
FUN_15(Speed 3)
OFF
OFF
ON
OFF
FUN_16(Speed 4)
ON
OFF
ON
OFF
FUN_17(Speed 5)
OFF
ON
ON
OFF
FUN_18(Speed 6)
ON
ON
ON
OFF
FUN_19(Speed 7)
X
X
X
ON
FUN_20(Jog Speed)
1.2) MOP (Motor operated potentiometer) Up / MOP Down / MOP Clear / MOP Save
When multi-function input terminals P1 ~ P7 is set to
“
MOP Up
”
,
“
MOP Down
”
, inverter performs Accel/Decel
Constant Run according to the terminal input. Generally, MOP function is used to adjust the speed simply with
terminal ON/OFF. When MOP UP/Down is selected, inverter ignores FUN_02 setting, and performs MOP operation. To
cancel it, change the defined terminal to
“
Not Used
”
. If this function is selected with
“
Main Drive
”
function, operating
reference is done by MOP and the rest will be defined by
“
Main Drive
”
function. Max speed limit is FUN_04(Max
Speed).
If
“
MOP Save
”
is entered during MOP operation, the current speed reference value is saved as
”
MOP Data
”
and
retained. When the MOP operation resumes, the retained value will be used as speed reference.
“
MOP Clear
”
resets the MOP Data value to
“
0
”
. It is used to change the saved value.