6. Function Description
6-22
Code
Display
Description
Range
Unit
Default
DIO_57
OL level
Overload warning level
30 ~ 250
%
150
DIO_58
OL time
Overload warning time
0 ~ 30
sec
10
Note:
The set value of overload alarm level is of percentage(%) to the rated current of the motor.
2.16) Stop
‘
Stop
’
is ON when the inverter keeps stopping.
2.18) MC on/Off
This function control the operation of magnetic contactor (MC) when MS is mounted on the inverter output at the
application, elevator, etc. It is the multiple functional output signal that it turns on/off the contact of MC before a
current is outputted from inverter at start.
LED of FWD and REV on keypad flikers during the time of MC on/off. If MC on/off is not set at multi-function output,
operation will be same as the setting of MC on/off time = 0.
Code
Display
Description
Range
Unit
Default
DIO_67
MC Timer On
Delayed time of MC On
100~50000
msec
1000
DIO_68
MC Timer Off
Delayed time of MC Off
100~50000
msec
1000
Multi-function
output (OverLoad)
Overload warning signal
T1
TIME
T1
I/O_58
ON
OFF
OFF
Output current
current