6. Function Description
6-82
2)
Adjusting Gain and Bias by Keypad
AIO_76 AO1 Bias setting
It can be set the Bias value of analog output value. It can occur actual output more than the Bias value.
Key
LCD Display
Description
Initial Gain (Factory setting)
PROG
When pressing the [PROG] key, current output [%] to input
value is displayed on the first line and current setting bias
on the second line.
▲
If you want to adjust Bias so that output is occurs when is
more than 30% , adjust it to be 30.0% using [
▲
(Up)] key.
ENT
After adjusting Bias and pressing [ENT] key, it is displayed
and the changed value is saved.
AIO_77 AO1 Gain setting
You can set the slope of output so that max. output of analog output can be 10V.
Key
LCD Display
Description
Initial Gain (Factory setting)
PROG
When pressing the [PROG] key, current output [%] to input
value is displayed on the first line and current setting gain
on the second line.
▲
If you want to adjust Gain to be 10V output at more than
200% on the first line, adjust gain to be 200.0% using [
▲
(Up)] key.
ENT
After setting 102.00% Gain and pressing [ENT] key, it is
displayed and the changed gain is saved.
In examples for output setting of multi-function analog output, according to setting of Bias, Gain and the absolute
value at
-10 ~ 10V input, the output waveform varies as below.
AIO
▶
A01 Bias
76 0.0 %
AIO
▶
Ao1 0.18 %
76 Bias
0.00 %
AIO
▶
Ao1 0.00 %
76 Bias
30.0 %
I/O
▶
A01 Bias
76 30.0%
AIO
▶
AO1 Gain
77 100.0 %
AIO
▶
Ao1
30.0 %
77 Gain 100.0 %
AIO
▶
Ao1 30.0 %
77 Gain
200.0 %
AIO
▶
AO1 Gain
77 200.00 %