3. Installation and Wiring
3-22
Item
Name
Function
Description
30A
Fault alarm
A contact
Outputs when fault occurs.
Deactivated in BX condition.
30B
Fault alarm
B contact
30C
COMMON
COMMON for A, B
Switch
JP1
Encoder Input-
pulse Type
LD (Line Drive) /
OC (Open Collector or Complementary)
JP2
Encoder Power
Supply
DC +5V / +12V / +15V selectable usages
JP4
PNP/NPN Input
mode
PNP/NPN contact input mode selection
Note)
1) Example wiring of Encoder output
Warning!
Wiring must be
considered with input
circuit . Because
encoder output is open
collector type.
The figure is shown the
wiring when inverter is
connected with High-
speed counter of LS
ELECTRIC PLC.
Vcc
Encoder Output
(SIO return
pulse)
RA
GE
RB
GE
Peripheral device
(e.g: PLC High-speed
Counter
A-phase input
A-phase
COM
B-phase input
B-phase
COM
GND