3. Installation and Wiring
3-20
Item
Name
Function
Description
AI2
Motor NTC is selectable function.
Jumper setting in Voltage Input:
Jumper set
as default)
AI1, AI2: Jumper set on left side,
AI3: Switch set on left
(“V”) side
Jumper setting in Current Input
AI1, AI2: Jumper set on right side
S/W setting in motor NTC (Higen motor)
AI3: switch set on right
(“Them”) side.
Selectable 17 functions as following:
(Speed, Process PID controller, Process PI
controller feedback, Draw, Torque, Magnetic
flux, Torque bias, Torque limit, Motor NTC,
etc.)
AI3/
Them
Voltage input
Motor NTC Input
5G
COMMON
COMMON terminal for Analog input
Encode
r Inpu
t
PE
P/S (Power
supply) for Pulse
Encoder
+5V Line Drive Power
GE
0V
A+
Encoder
A-phase signal
A, B signal for Line Drive Type Encoder.
Set the JP2
switch at “P5” on I/O PCB and
set the JP4 switch to “LD” for the use of Line
Drive.
※
Jumper set as default
A-
B+
Encoder
B-phase signal
B-
PE
P/S for Open
Collector
+15V Open Collector Power
GE
0V
PA
Encoder
A-phase signal
A, B signal for Complementary or Open
Collector Type Encoder.
Set the JP2 switch at “P15” on I/O PCB and
set the JP4 switch to “OC” for the use of
Open Collector.
PB
Encoder
B-phase signal
Z+
(PZ)
Encoder
Z-phase signal
Caution) The usages of Z-phase signal are
as follows and its functions will
be available soon.
Use for Z-phase pulse provided encoders.
Z+ and Z- signals are used for Line Drive
type, so set the JP5 switch to “LD”.
PZ signal is used for Open Collector type, so
set the JP5 switch to “OC”.
Z-
Содержание LSLV-iV5 Series
Страница 59: ...4 Trial Operation 4 17 ...
Страница 285: ......