6. Function Description
6-25
3) DIO_46 (Fault output relay (30A, 30B, 30C))
This function can be used when the inverter fault signal is generated through the relay contact. the fault alarm is
triggered differently by setting the bits related to the low voltage trip, inverter trip and the number of retry.
Code
Display
Description
Range
Unit
Default
DIO_46
Relay mode
Relay mode
000 ~ 111
-
011
Code
Bit 2
(Number of Auto retry)
Bit 1
(Inverter trip)
Bit 0
(LV trip)
DIO_46
0/1
0/1
0/1
Bit
Setting
Description
Bit 0
(LV)
0
Deactivated at Low Voltage Trip
1
Activated at Low Voltage Trip
Bit 1
(Trip)
0
Deactivated at any fault
1
Activated at any fault except Low Voltage Trip
Bit 2
(Retry)
0
Deactivated at the auto retry attempt
1
Activated at the number of auto retry attempt
4) DIO_59 ~ 61 (Overload trip enable, level, time)
If the inverter output current higher than the overload limit level is kept for the overload limit time, the inverter
blocks the gating of IGBTs and issues the trip message.
Code
Display
Description
Range
Unit
Default
DIO_59
OLT select
Overload trip enable
Yes/No
-
Yes
DIO_60
OLT level
Overload trip level
30 ~ 250
%
180
DIO_61
OLT time
Overload trip time
0 ~ 60
sec
60
Note: DIO_60 is set as the percentage of Motor rated current.
5) DIO_97(Operation method when losing command)
You can choose the operation method when multi-function analog input signal satisfying the criteria
(AIO_12/24/36/48/60/72 Ai1/2/3/4/5/6 Wbroken) for judging time (AIO_73 Time Out) or satisfying the
command loss condition of communication option card. Refer to analog I/O Group for the criteria for the
multi-function analog input signal loss and the judging time of signal loss.
If Lost Command is happed after operation stop then the condiiton of Lost Command is released, the
operation is not automatically start. In case of terminal operation, FX is turned Off and then turned On to
operate. Push down the FWD/REV key to operated in keypad operation.
Code
Display
Function Name
Unit
Description
Range
DIO_97 Lost Command
None
-
Continuing the operation when losing command
Free-run
-
Free-run stop when losing command
Stop
-
Decelerating stop when losing command