5. Function Code Table
5-6
CODE
NO.
Comm.
Addr
CODE NAME
LCD
DISPLAY
SETTING DATA
Adjustment
During Run
RANGE
UNIT DEFAULT
DIO_62 723E
Inverter overheat
warning temp.
IH Warn
Temp
50 ~ 85
deg
75
Yes
DIO_63 723F
Inverter overheat
warning band
IH Warn
Band
0 ~ 10
deg
5
Yes
DIO_64 7240
Motor overheat
warning temp.
MH Warn
Temp
75 ~ 130
deg
120
Yes
DIO_65 7241
Motor overheat
warning band
MH Warn
Band
0 ~ 10
deg
5
Yes
DIO_67 7243
MC ON
delay time
4)
MC Timer
Off
100~50000
msec
1000
No
DIO_68 7244
MC OFF
delay time
4)
MC Timer
Off
100~50000
msec
1000
No
DIO_95 725F
Inverter station
address
Inv
Number
1~250
1
No
DIO_96 7260
485 BaudRate
485
BaudRate
0 (1200)
bps
9600
No
1 (2400)
2 (4800)
3 (9600)
4 (19200)
5 (384000)
DIO_97 7261
How to Run at
Lost command
Lost
Command
0 (None)
-
0
(None)
No
1 (FreeRun)
2 (Stop)
DIO_98 7262
Decision time
when
communication
command is lost.
4)
Comm.
Timer
10~300
sec
10
No
Note)
1) Displayed WEB Control mode setting.
2) It can be set at 5.5 ~ 22 kW-2/4 class.
3) It will be displayed as CON_02 sets to
‘Synchro’ when Synchronization option board is
installed.
4) It will be displayed when the definition of multi-funtion output sets as
‘MC On/Off’.
5) It will be displayed RS-485 communication option board is installed. Refer to the user manual
for RS485/Modbus-RTU option board (iP5A/iV5).