3. Installation and Wiring
3-13
3.3.2 Power circuit terminal description
(1) AC power input type
Name
Function
Description
R, S, T
3 Phase input
power supply
Connected to 3 phase input power supply
U, V, W Inverter Output
Connected to 3 phase induction motor
G
Grounding
Used for inverter frame earth
B1, B2 Braking Resistor
Connected to braking resistor
P1(+),
P2(+)
DC Reator and DB
Unit
Used for DC Reactor, DB Unit and
DC link common connection
P(+)
DC Link common
DC link common connection
N(-)
DB Unit
Used for DB Unit and DC link common
connection
(2) DC power input type
Name
Function
Description
P(+),
N(-)
DC input power
Connected to DC input power source
Connected from DC power suupy (PWM
converter) within max. 30m
U, V, W Inverter Output
Connected to 3-phase induction motor
G
Grounding
Used for inverter frame earth
FAN1,
FAN2
Internal cooling fan
and MC drive power
source
Connected to single-phase 220V AC
power source
note1)
Note 1) In case of 500kW product, it is applied at AC input type.
3.3.3 Cautions to be required for wiring to power circuit terminal
①
Connect terminals (R, S and T) to 3 phase input power supply after checking
inverter nameplate attached on the inverter. Never connect terminals (U, V
and W) to 3 phase input power supply. It results in lethal damage to the
inverter.
Input
Voltage
R S T G U V W