the automatic running when powering
1: Enable, if the starting need is met, will
This function can enable start or not after
will run automatically.
one, will pause to stand by.
frequency is lower than the lower limit
, will come
Function Parameters
45
Function
code
Name
Description
Default
value
Modify
limit of
frequency is
larger than 0)
is lower than the lower-limit one. If the set
frequency is above the lower limit one again and it
lasts for the time set by
back to the running state automatically.
3: Sleep and standby 2
Select sleep and standby 2: When the running
frequency is no more than lower limit frequency
continuously before entering sleep state.
Setting range: 0
–3
E01.20
Wake-up-from-
sleep delay
This function code determines the
wake-up-from-sleep delay. When the running
When the set frequency is above the lower limit
one again and it lasts for the time set by
Note:
The time is the total value when the set
frequency is above the lower limit one.
Setting frequency
running
dormancy
t1
t2
running
t
t1
<
t3, so the VFD does not work
t1+t2=t3, so the VFD works
t3=E01.20
t3
Setting range: 0.0
–3600.0s
(valid when
=2)
0.0s
○
E01.21
Restart after
power off
the power off and then power on.
0: Disable
run automatically after waiting for the time defined
0
○
E01.22
The waiting
time of restart
after power off
The function determines the waiting time before
off and then powering on.
1.0s
○