valid, ceases the output immediately. And
frequency decreases to 0Hz, stops.
becomes valid, decelerates to reduce the
Function Parameters
42
Function
code
Name
Description
Default
value
Modify
E01.05
ACC/DEC
selection
The changing mode of the frequency during start
and running.
0: Linear type
The output frequency increases or decreases
linearly.
fmax
Output frequency
t1
t2
t
t1=E00.11/E08.00/
E08.02/E08.04
t2=E00.12/E08.01/
E08.03/E08.05
1: S curve:
Output frequency increases/decreases gradually
based on S curve. S curve is used in cases where
smooth start/stop is required, such as elevator,
conveyer belt, etc.
Output frequency
t
t1
t2
t1
t2
t1=E01.06
t2=E01.07
0
◎
E01.06
ACC time of the
starting step of
S curve
Setting rage: 0.0
–50.0s
Note: Effective when
= 1
0.1s
○
E01.07
DEC time of the
ending step of
S curve
0.1s
○
E01.08
Stop mode
0: Decelerate to stop: after the stop command
output frequency during the set time. When the
1: Coast to stop: after the stop command becomes
the load coasts to stop at the mechanical inertia.
0
○
E01.09
Starting
frequency of
DC braking
Starting frequency of DC braking: start the DC
braking when running frequency reaches starting
frequency determined by
0.00 Hz
○
E01.10
Waiting time
0.00s
○