The DC bus capacitors must be reformed according to the operation instruction if
diagram
consistent with that
designated.
. Stop and disconnect it from the AC
Fault Tracking
125
8.8.2.1 Replacing the cooling fan
Read and follow the instructions in chapter
Safety Precautions
. Ignoring
the instructions would cause physical injury or death, or damage to the
equipment.
1
power source and wait for at least the time
2
. Lever the fan holder off the drive frame with a screwdriver and lift the hinged fan holder slightly
upward from its front edge.
3
. Loose
the fan cable from the clip.
4
. Disconnect the
fan cable.
5
. Remove the fan holder from the hinges.
6
. Install the new fan holder including the fan in reverse order. Keep the wind direction of the fan
, as shown below:
Rotation
direction
Wind
direction
Wind
direction
Rotation
direction
Wind
direction
Wind
direction
Fan maintenance
7
. Restore power.
8.8.3 Capacitors
8.8.3.1 Reforming the capacitors
has
been stored for a long time. The storing time is counted form the producing date other than the
delivery data which has been marked in the serial
.
Time
Operational principle
Storing time less than 1 year Operation without charging
Storing time 1-2 years
Connect with the power for 1 hour before first ON command
Storing time 2-3 years
• Apply 25% rated voltage for 30 minutes
• Apply 50% rated voltage for 30 minutes
• Apply 75% rated voltage for 30 minutes
• Apply 100% rated voltage for 30 minutes
Storing time more than 3 years
• Apply 25% rated voltage for 2 hours
• Apply 50% rated voltage for 2 hours
• Apply 75% rated voltage for 2 hours
• Apply 100% rated voltage for 2 hours
The method of using