Product Overview
8
3.
The 037G/045P and higher models can be installed with optional braking units and the braking
unit and resistor are optional.
3.3 Product specification
Function
Specification
Input
Input voltage (
V
)
AC 3PH 220V(-15%)
–240V(+10%)
AC 3PH 380V(-15%)
–440V(+10%)
AC 3PH 520V(-15%)
–690V(+10%)
Input current (
A
)
Refer to
the
product rated value
Input frequency (
Hz
)
50Hz or 60Hz
Allowed range: 47
–63Hz
Output
Output voltage (
V
)
0
–Input voltage
Output current (
A
)
Refer to
the product rated value
Output power (
kW
)
Refer to
the product rated value
Output frequency (
Hz
) 0
–400Hz
Technical
control
feature
Control mode
SVPWM, SVC
Motor type
Asynchronous motor
Speed ratio
Asynchronous motor 1: 100 (SVC)
Speed control
accuracy
±0.2% (sensorless vector control)
Speed fluctuation
± 0.3%(sensorless vector control)
Torque response
<20ms(sensorless vector control)
Torque control
accuracy
10%(sensorless vector control)
Starting torque
Asynchronous motor: 0.5Hz/150% (SVC)
Overload capability
G type:
150% of rated current: 1 minute
180% of rated current: 10 seconds
200% of rated current: 1 second
P type:
120% of rated current: 1 minute
180% of rated current: 10 seconds
180% of rated current: 1 second
Running
control
feature
Frequency setting
Digital setting, analog setting, pulse frequency setting,
multi-step speed running setting, simple PLC setting,
PID setting, MODBUS communication setting.
Shift between the set combination and set channel.
Auto voltage
adjustment
Keep a stable voltage automatically when the grid
voltage transients
Fault protection
Provide over 30 fault protection functions: overcurrent,
overvoltage, undervoltage, overheating, phase loss
and overload, etc.