E00.01
E00.00
f E07.00 is not 0 during powering on,
hen E07.00 is set to 0, the password can be
The control command includes: start,
Select the run command channel.
Function Parameters
34
W
canceled. I
then the parameter is protected by the password. When modify the parameters by serial
communication, the function of the password follows the above rules, too.
Function
code
Name
Description
Default
value
Modify
E00 Group Basic functions
Speed control
mode
1: Sensorless vector control mode 1 (applying to
AM)
No need to install encoders. It is suitable in cases
with high speed control accuracy for accurate
speed and torque control at all power ratings.
2: SVPWM control
No need to install encoders. It can improve the
control accuracy with the advantages of stable
operation, valid low-frequency torque boost and
current vibration suppression and the functions of
slip compensation and voltage adjustment.
Note
: AM-Asynchronous motor
2
◎
Run command
channel
stop, forward, reverse, jogging and fault reset.
0: Keypad running command
channel("LOCAL/REMOT" light off)
Carry out the command control by RUN,
STOP/RST on the keypad.
Set the multi-function key QUICK/JOG as
FWD/REV shifting function (
=3) to change
the running direction; press
RUN
and
STOP/RST
simultaneously in running state to make the VFD
coast to stop.
1: Terminal running command channel
("LOCAL/REMOT" flickering)
Carry out the running command control by the
forward rotation, reverse rotation and forward
jogging and reverse jogging of the multi-function
terminals
2: Communication running command channel
("LOCAL/REMOT" on);
The running command is controlled by the upper
monitor via communication.
0
○
E00.02 Communication 0: MODBUS communication
0
○