will run according to parameter
rotation and reverse rotation, does not
Function Parameters
69
Function
code
Name
Description
Default
value
Modify
5: Coast to stop. Press
to coast to
stop.
6: Shift the running commands source. Press
to shift the running commands
source.
7: Quick commission mode(committee according
to the non-factory parameter)
Note:
Press
to shift between forward
record the state after shifting during powering off.
E00.13
during next powering on.
Tens: Keypad lock selection
0: Do not lock keypad buttons
1: Lock all the keypad buttons
2: Lock part of the keypad buttons (lock PRG/ESC
key only)
Note: If the tens is 1, press PRG+DAT keys three
times, and all the keypad buttons will be locked;
Keep DAT key pressed down while pressing V key
three times can unlock keypad buttons.
Setting range: 0x00
–0x27
E07.03
Shifting
sequence
selection of
commands
When
=6, set the shifting sequence of
running command channels.
0: Keypad contr
ol→terminals control
→communication control
1: Keypad control←→terminals control
2: Keypad control←→communication control
3: Terminals control←→communication control
0
○
E07.04
STOP/RST
stop function
STOP/RST is valid for stop function. STOP/RST
is valid in any state for the fault reset.
0: Only valid for the keypad control
1: Both valid for keypad and terminals control
2: Both valid for keypad and communication
control
3: Valid for all control modes
0
○
E07.05
Parameters
state 1
0x0000
–0xFFFF
BIT0: running frequency (Hz on)
BIT1: set frequency (Hz flickering)
BIT2: bus voltage (Hz on)
0x03FF
○
ME.K
ME.K
ME.K
ME.K