, will
Function Parameters
84
Function
code
Name
Description
Default
value
Modify
Output frequency
T
T
Feedback value
Bias limit
Reference value
Setting range: 0.0
–100.0%
E09.09
Output upper
limit of PID
These parameters are used to set the upper and
lower limit of the PID adjustor output.
100.0 % corresponds to max. frequency or the
max. voltage of (
–100.0%
: -100.0%
100.0%
○
E09.10
Output lower
limit of PID
0.0%
○
E09.11
Feedback
offline detection
value
Set the PID feedback offline detection value, when
the detection value is smaller than or equal to the
feedback offline detection value, and the lasting
time exceeds the set value in
report "PID feedback offline fault" and the keypad
will display PIDE.
T
Output frequency
t1
t2
E09.11
T1
<
T2, so the VFD
continues to work
t2=E09.12
Running
Fault output PIDE
PIDE
: 0.0
–100.0%
: 0.0
–3600.0s
0.0%
○
E09.12
Feedback
offline detection
time
1.0s
○
E09.13 PID adjustment
0x0000
–0x1111
LED ones:
0: Keep on integral adjustment when the
frequency achieves the upper and low limit; the
integration shows the change between the
reference and the feedback unless it reaches the
internal integral limit. When the trend between the
reference and the feedback changes, it needs
more time to offset the impact of continuous
0x0001
○