Function Parameters
63
Function
code
Name
Description
Default
value
Modify
E05.41
AI2 input filter
time
Corresponding
setting
100%
-100%
-10V
Al3
AI1/AI2
20mA
AI
10V
Input filter time: this parameter is used to adjust
the sensitivity of the analog input. Increasing the
value properly can enhance the anti-interference
of the analog, but weaken the sensitivity of the
analog input
Note:
Analog AI1 and AI2 can support 0
–10V or
0
–20mA input, when AI1 and AI2 selects 0–20mA
input, the corresponding voltage of 20mA is 10V.
AI3 can support the input of -10V
–+10V.
: 0.00V
: -100.0%
–100.0%
–10.00V
: -100.0%
–100.0%
: 0.000s
–10.000s
: 0.00V
: -100.0%
–100.0%
–10.00V
: -100.0%
–100.0%
: 0.000s
–10.000s
: -10.00V
: -100.0%
–100.0%
: -100.0%
–100.0%
Setting range of
–10.00V
: -100.0%
–100.0%
: 0.000s
–10.000s
0.100s
○
E05.42
Lower limit of
AI3
-10.00V
○
E05.43
Corresponding
setting of the
lower limit of
AI3
-100.0%
○
E05.44
Middle value of
AI3
0.00V
○
E05.45
Corresponding
middle setting
of AI3
0.0%
○
E05.46
Upper limit of
AI3
10.00V
○
E05.47
Corresponding
setting of
the upper limit
of AI3
100.0%
○
E05.48
AI3 input filter
time
0.100s
○
E05.50
Lower limit
frequency of
HDI
0.000kHz
0.000
kHz
○
E05.51
Corresponding
setting of HDI
low frequency
-100.0%
–100.0%
0.0%
○