Provide 3 channels
runs at the lower limit frequency if the set
upper limit of the output frequency
frequency. Users should pay attention
Function Parameters
35
Function
code
Name
Description
Default
value
Modify
selection
1
–3: Reserved
E00.03
Max. output
frequency
This parameter is used to set the Maximum output
to this parameter because it is the foundation of
the frequency setting and the speed of
acceleration and deceleration.
Setting range:
–400.00Hz
50.00
Hz
◎
E00.04
Upper limit of
the running
frequency
The upper limit of the running frequency is the
which is lower than or equal to the maximum
frequency.
Setting range:
(max. output
frequency)
50.00
Hz
◎
E00.05
Lower limit of
the running
frequency
The lower limit of the running frequency is that of
the output frequency
frequency is lower than the lower limit one.
Note:
Max. output frequency ≥ Upper limit
frequency ≥ Lower limit frequency
Setting range: 0.00Hz
(Upper limit of the
running frequency)
0.00Hz
◎
E00.06
A frequency
command
Note:
Frequency A and frequency B cannot use
the same frequency setting mode. The frequency
source can be set by
0: Keypad data setting
Modify the value of
keypad) to modify the frequency by the keypad.
1: Analog AI1 setting (implemented through the
analog potentiometer on the keypad for the
0150G/018P and lower models; not available for
the 018G/022P and higher models.)
2: Analog AI2 setting
3: Analog AI3 setting
Set the frequency by analog input terminals.
analog input terminals as the standard
configuration, of which AI1/AI2 are the
voltage/current option (0
–10V/0–20mA) which can
be shifted by jumpers; while AI3 is voltage input
(-10V
–+10V).
0
○
E00.07
B frequency
command
2
○