E00.03
E00.03
when several drive one load.
Function Parameters
77
Function
code
Name
Description
Default
value
Modify
ratio of the
dropping
control
Setting range: 0.00
–10.00Hz
E08.32
FDT1 electrical
level detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level,
the multi-function digital output terminals will
output the signal of "frequency level detect FDT"
until the output frequency decreases to a value
lower than (FDT electrical level
—FDT retention
detection value) the corresponding frequency, the
signal is invalid. Below is the waveform diagram:
Output frequency
FDT level
Y,
RO1, RO2
FDT lag
: 0.00Hz
–
(the max. frequency)
: 0
–100.0%
(FDT1 electrical level)
: 0.00 Hz
–
(the max. frequency)
: 0.0
–100.0%
(FDT2 electrical level)
50.00
Hz
○
E08.33
FDT1 retention
detection value
5.0%
○
E08.34
FDT2 electrical
level detection
value
50.00
Hz
○
E08.35
FDT2 retention
detection value
5.0%
○
E08.36
Amplitude
value for
frequency
arrival
detection
When the output frequency is among the below or
above range of the set frequency, the
multi-function digital output terminal will output the
signal of "frequency arrival", see the diagram
below for detailed information:
0.00 Hz
○