and must be the same. Otherwise, the
upper monitor .
150.0%
during the stopping, set
=0 during the starting, set
Function Parameters
92
Function
code
Name
Description
Default
value
Modify
running frequency more than
, ACC/DEC
time switch to step 2 ACC/DEC time
E13 Group Enhanced function parameters
E13.13
Braking current
of short-circuit
When
to a non-zero value to enter the short
circuit braking.
When the running frequency is lower than
E13.15
to a
non-zero value to enter into stopping short
circuited braking and then carry out the DC
braking at the time set by
instruction of
: 0.0
–
: 0.00
–50.00s
: 0.00
–50.00s
0.0%
○
E13.14
Braking
retention time
before starting
0.00s
○
E13.15
Braking
retention time
when stopping
0.00s
○
E14 Group Serial communication
E14.00
Local
communication
address
The setting range: 1
–247
When the master is writing the frame, the
communication address of the slave is set to 0; the
broadcast address is the communication address.
All slaves on the MODBUS fieldbus can receive
the frame, but the salve doesn’t answer.
The communication address of the drive is unique
in the communication net. This is the fundamental
for the point to point communication between the
upper monitor and the drive.
Note:
The address of the slave cannot set to 0.
1
○
E14.01
Communication
baud ratio
Set the digital transmission speed between the
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
7: 115200BPS
Note:
The baud rate between the upper monitor
communication is not applied. The bigger the baud
rate, the quicker the communication speed.
4
○