Fault Tracking
113
Fault code
Fault type
Possible cause
What to do
OC2
Over-current when
deceleration
The voltage of the grid is
too low
The pow
low
The load transients or is
abnormal
The grounding is short
circuited or the output is
phase loss
There is strong external
interference
The overvoltage stall
protection is not open
Select t
larger
power
Check if the load is short
circuited (the grounding
short circuited or the wire
short circuited) or the
rotation is not smooth
Check the output
configuration.
Check if there is strong
interference
Check the setting of relative
function codes
OC3
Over-current when
constant speed
running
OV1
Over-voltage when
acceleration
The input voltage is
abnormal
There is large energy
feedback
No braking components
Braking energy is not open
Check the input power
Check if the DEC time of
the load is too short or the
rotation of the motor or it
needs to add the dynamic
braking components
Install the braking
components
Check the setting of relative
function codes
OV2
Over-voltage when
deceleration
OV3
Over-voltage when
constant speed
running
UV
DC bus
Under-voltage
The voltage of the power
supply is too low
The overvoltage stall
protection is not open
Check the input power of
the supply line
Check the setting of relative
function codes
OL1
Motor overload
The voltage of the power
supply is too low
The motor setting rated
current is incorrect
The motor stall or load
transients is too strong
Check the power of the
supply line
Reset the rated current of
the motor
Check the load and adjust
the torque lift
OL2
VFD overload
The acceleration is too fast
Reset the rotating motor
The voltage of the power
supply is too low
The load is too heavy
The motor power is too
small
Increase the ACC time
Avoid the restarting after
stopping
Check the power of the
supply line
power
Select a proper motor