won’t work when the stopping command
terminal is valid, stop because
Function Parameters
60
Function
code
Name
Description
Default
value
Modify
The direction control is as below during operation:
Sln
REV
Previous
direction
Current
direction
ON
OFF→ON
Forward
Reverse
Reverse
Forward
ON
ON→OFF
Reverse
Forward
Forward
Reverse
ON→
OFF
ON
Decelerate to stop
OFF
3: 3-wire control 2; Sin is the enabling terminal on
this mode, and the running command is caused by
SB1 or SB3 and both of them control the running
direction. NC SB2 generates the stop command.
COM
SB2
SB1
FWD
REV
SIn
SB3
Sln
FWD
REV
Direction
ON
OFF→
ON
ON
Forward
OFF
Reverse
ON
ON
OFF→
ON
Forward
OFF
Reverse
ON→
OFF
/
/
Decelerate
to stop
/
/
Note
: for the 2-wire running mode, when
FWD/REV
of the stopping command from other sources,
even the control terminal FWD/REV keeps valid;
is canceled. Only when FWD/REV is relaunched,
can start again. For example, the valid
STOP/RST stop when PLC signal cycles stop,
fixed-length stop and terminal control (see