Display current ramp reference frequency
Display current output frequency
Display current set frequency
Function Parameters
94
Function
code
Name
Description
Default
value
Modify
communication state.
E14.05
Transmission
fault processing
0: Alarm and stop freely
1: No alarm and continue to run
2: No alarm and stop according to the stop means
(only under the communication control)
3: No alarm and stop according to the stop means
(under all control modes)
0
○
E14.06
Communication
processing
LED ones place:
0: Operation with response: the drive will respond
to all reading and writing commands of the upper
monitor.
1: Operation without response; The drive only
responds to the reading command other than the
writing command of the drive. The communication
efficiency can be increased by this method.
LED tens place:
0: Communication encrypting invalid
1: Communication encrypting valid
LED hundreds place, indicating RS485
communication device type
Note: When the LED hundreds place is 1, E14.07
and E14.08 are valid.
0x00
○
E14.07
User-defined
address of
running
commands
0x0000
–0xffff
0x1000
○
E14.08
User-defined
address of
frequency
setting
0x0000
–0xffff
0x2000
○
E17 Group Monitoring function
E17.00
Setting
frequency
Range: 0.00Hz
–E00.03
/
●
E17.01
Output
frequency
Range: 0.00Hz
–E00.03
/
●
E17.02
Ramp
reference
/
●