E00.03
E00.03
Communication Protocol
141
Function
instruction
Address
definition
Data meaning instruction
R/W
characteristics
Identifying code
of the VFD
2103H
0x0107
R
Operation
frequency
3000H
Range: 0.00Hz
–
R
Setting
frequency
3001H
Range: 0.00Hz
–
R
Bus voltage
3002H
Range: 0
–1200V
R
Output voltage
3003H
Range: 0
–1200V
R
Output current
3004H
Range: 0.0
–5000.0A
R
Operation speed
3005H
Range: 0
–65535RPM
R
Output power
3006H
Range: -300.0
–300.0%
R
Output torque
3007H
Range: 0
–65535RPM
R
Close loop
setting
3008H
Range: -100.0%
–
100.0%
R
Close loop
feedback
3009H
Range: -100.0%
–
100.0%
R
Input IO state
300AH
Range: 0000
–00FF
R
Output IO state
300BH
Range: 0000
–00FF
R
AI 1
300CH
Range: 0.00
–10.00V
R
AI 2
300DH
Range: 0.00
–10.00V
R
AI 3
300EH
Range: 0.00
–10.00V
R
AI 4
300FH
Reserved
R
Read high speed
pulse 1 input
3010H
Range: 0.00
–50.00kHz
R
Read high speed
pulse 2 input
3011H
Reserved
R
Read current
step of multi-step
speed
3012H
Range: 0
–15
R
External length
3013H
Range: 0
–65535
R
External
counting value
3014H
Range: 0
–65535
R
Torque setting
3015H
Range: 0
–65535
R
VFD code
3016H
R
Fault code
5000H
R
R/W characteristics means the function is with read and write characteristics. For example,
"communication control command" is writing chrematistics and control the VFD with writing
command (06H). R characteristic can only read other than write and W characteristic can only write
other than read.