E00.03
Function Parameters
55
Function
code
Name
Description
Default
value
Modify
slip frequency of the motor which is counted as
below:
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor, its
function code is
; n is the rated rotating
speed of the motor and its function code is
p is the pole pair of the motor. 100.0%
corresponds to the rated slip frequency
△
f.
Setting range: 0.0
–200.0%
E04.10
Motor 1 low
frequency
vibration
control factor
In the SVPWM control mode, current fluctuation
may occur to the motor on some frequency,
especially the motor with big power. The motor
cannot run stably or overcurrent may occur. These
phenomena can be canceled by adjusting this
parameter.
: 0
–100
: 0
–100
: 0.00Hz
–
(the max. frequency)
10
○
E04.11
Motor 1 high
frequency
vibration
control factor
10
○
E04.12
Motor 1
vibration
control
threshold
30.00
Hz
○
E04.26
Energy-saving
operation
selection
0: No action
1: Automatic energy-saving operation
Motor on the light load conditions, automatically
adjusts the output voltage to save energy
0
◎
E04.27
Voltage setting
channel
Select the output setting channel at V/F curve
separation.
0: Keypad setting voltage: the output voltage is
determined by
1: AI1 setting voltage (implemented through the
analog potentiometer on the keypad for the
0150G/018P and lower models; not available for
the 018G/022P and higher models.)
2: AI2 setting voltage;
3: AI3 setting voltage;
4: HDI setting voltage;
5: Multi-step speed setting voltage;
6: PID setting voltage;
7: MODBUS communication setting voltage;
Note:
100% corresponds to the rated voltage of
the motor.
0
○