ACC/DEC time which can be selected by E05. The
factory default ACC/DEC time of the
1: Runs at the opposite direction,runs in
0: Runs at the default direction, runs in
define four groups of
Function Parameters
38
Function
code
Name
Description
Default
value
Modify
E00.12
DEC time 1
first group.
: 0.0
–3600.0s
Depend
on
model
○
E00.13
Running
direction
the forward direction. FWD/REV indicator is off.
the reverse direction. FWD/REV indicator is on.
Modify the function code to shift the rotation
direction of the motor. This effect equals to the
shifting the rotation direction by adjusting either
two of the motor lines (U, V and W). In keypad
control, the motor rotation direction can be
changed by
on the keypad. Refer to
parameter
Note:
When the function parameter comes back to
the default value, the motor’s running direction will
come back to the factory default state, too. In
some cases it should be used with caution after
commissioning if the change of rotation direction is
disabled.
2: Forbid to run in reverse direction: It can be used
in some special cases if the reverse running is
disabled.
0
○
E00.14
Carrier
frequency
setting
Carrier
frequency
Electro magnetic
noise
Noise and leakage
current
Heating
eliminating
High
Low
High
Low
High
Low
1kHz
10kHz
15kHz
Mapping between models and carrier frequencies:
Model
Factory setting
of carrier
frequency
0R7G
–011G/015P
8kHz
015G/018P
–055G/075P
4kHz
075G/090P and higher
2kHz
Depend
on
model
○
ME.K