VFDs can set 16 steps
Function Parameters
86
Function
code
Name
Description
Default
value
Modify
E10.01
Simple PLC
memory
0: Power loss without memory
1: Power loss memory; PLC record the running
step and frequency when power loss.
0
○
E10.02
Multi-step
speed 0
100.0% of the frequency setting corresponds to
the max. frequency E00.03.
When selecting simple PLC running, set
to define the running frequency
and direction of all steps.
Note:
The symbol of multi-step determines the
running direction of simple PLC. The negative
value means reverse rotation.
P10.04
P10.02
P10.03
P10.05
P10.07
P10.06
P10.31
P10.33
P10.32
ACC time
2 stages
DEC time
2 stages
P10.30
P10.28
Multi-step speeds are in the range of --f
max
–f
max
and it can be set continuously.
speed, selected by the combination of multi-step
terminals 1
–4, corresponding to the speed 0 to
speed 15.
Output frequency
Terminal 1
(16)
Terminal 2
(17)
Terminal 3
(18)
Terminal 4
(19)
When terminal1= terminal 2= terminal 3= terminal
4=OFF, the frequency input manner is selected via
code
. When all termi
nals aren’t
off, it runs at multi-step which takes precedence of
keypad, analog value, high-speed pulse, PLC,
0.0%
○
E10.03
Running time of
step 0
0.0s
○
E10.04
Multi-step
speed 1
0.0%
○
E10.05
Running time of
step 1
0.0s
○
E10.06
Multi-step
speed 2
0.0%
○
E10.07
Running time of
step 2
0.0s
○
E10.08
Multi-step
speed 3
0.0%
○
E10.09
Running time of
step 3
0.0s
○
E10.10
Multi-step
speed 4
0.0%
○
E10.11
Running time of
step 4
0.0s
○
E10.12
Multi-step
speed 5
0.0%
○
E10.13
Running time of
step 5
0.0s
○
E10.14
Multi-step
speed 6
0.0%
○
E10.15
Running time of
step 6
0.0s
○
E10.16
Multi-step
speed 7
0.0%
○
E10.17
Running time of
step 7
0.0s
○
E10.18
Multi-step
speed 8
0.0%
○
E10.19
Running time of
step 8
0.0s
○