Fault Tracking
117
8.6 Common fault analysis
8.6.1 The motor does not work
The motor does not rotate
If the POWER is on or not?
If there is displaying on the keypad
If the contactor switches on the
input side
Switch on the air contactor
Check the voltage of
RST with multimeter
VFD fault
Check the voltage of the
power supply
If the keypad displays the
information or not
Ensure the running command
channel
Press RUN to run
Normal running
Settle the fault according
to the fault information
Normal running
Normal running
If the speed command setting is
right or not
Normal running
Check the voltage of UVW
VFD fault
If the motor configuration is right
or not
Set a right motor
configuration
If the load is too heavy
Reduce the load if the motor
is locked caused by heavy
load
Motor fault
Yes
No
No
Yes
Yes
Normal
Yes
Yes
Normal
Abnormal
Normal
Communication
Terminal
Keypad
Yes
Abnormal
No
No
No
No
No
No
Normal
Normal
Abnormal
Yes
Normal
Abnormal
Yes
Check the state of the input terminal
Reset the parameters
If it is normal running
If the communication configuration
is right or not
If the communication parameter is
right or not?
Normal
running
Normal
Abnormal
If the running is normal or
not after switching on
the terminal
Abnormal
If the running is normal after setting a right speed
command
8.6.2 Motor vibration
Motor vibration or
abnormal noise
Check the motor parameter
or motor type is right or not
If a VFD fault occurs,
please contact INVT
Check if there is abnormal
vibration to the load
Check if there is abnormal
vibration to the reference
frequency
If set right V/F vibration
parameter or not
Perform parameter
autotune or not
Please set right
motor type and
parameters
Perform right
parameter autotune
Check the
reference
frequency
Check the load
Yes
No
Yes
No
Yes
Yes
No
Yes
No
Set right
parameters
No