(E03.02), the speed loop PI
ol performance.
output current and K is the motor
Function Parameters
48
Function
code
Name
Description
Default
value
Modify
running frequency is below 30Hz.
2: Variable frequency motor (without low speed
compensation) Because the heat-releasing effect
of the specific motors won’t be impacted by the
rotation speed, it is not necessary to adjust the
protection value during low-speed running.
E02.27
Motor 1 over
load protection
coefficient
Times of motor overload M = Iout/(In*K)
In is the rated current of the motor, Iout is the
protection coefficient.
So, the bigger the value of K is, the smaller the
value of M is. When M=116%, protection is
performed after motor overload lasts for 1 hour;
when M=150%, protection is performed after
motor overload lasts for 12 minutes; when
M=180%, protection is performed after motor
overload lasts for 5 minutes; when M=200%,
protection is performed after motor overload lasts
for 60 seconds; and when
M≥ 400%, protection is
performed immediately.
1
5
12
60
116%
200%
Time (min)
Current overload
multiple
150%
180%
Setting range: 20.0%
–120.0%
100.0%
○
E02.28
Correction
coefficient of
motor 1 power
Correct the power displaying of motor 1.
Only impact the displaying value other than the
contr
Setting range: 0.00
–3.00
1.00
●
E03 Group Vector control
E03.00
Speed loop
proportional
gain1
The parameters
only apply to
vector control mode. Below the switching
frequency 1
parameters are:
. Above the
20.0
○
E03.01
Speed loop
0.200s
○