Function Parameters
65
Function
code
Name
Description
Default
value
Modify
20: External fault valid
22: Running time arrival
23: MODBUS communication virtual terminals output
26: DC bus voltage establishment
27: Auxiliary motor 1
28: Auxiliary motor 2
E06.05
Polarity
selection of
output
terminals
The function code is used to set the pole of the
output terminal.
When the current bit is set to 0, output terminal is
positive.
When the current bit is set to 1, output terminal is
negative.
BIT0
BIT1
BIT2
BIT3
Y
HDO
RO1
RO2
Setting range: 0
–F
0
○
E06.06
Y1
switching-on
delay time
The function code defines the corresponding delay
time of the electrical level change during the
programmable terminal switching on and off.
Y electric level
Y valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
The setting range: 0.000
–50.000s
Note:
are valid only when
=1.
0.000s
○
E06.07
Y1
switching-off
delay time
0.000s
○
E06.08
HDO
switching-on
delay time
0.000s
○
E06.09
HDO
switching-off
delay time
0.000s
○
E06.10
RO1
switching-on
delay time
0.000s
○
E06.11
RO1
switching-off
delay time
0.000s
○
E06.12
RO2
switching-on
delay time
0.000s
○
E06.13
RO2
switching-off
delay time
0.000s
○