voltage
(relative to twice rated current)
Function Parameters
66
Function
code
Name
Description
Default
value
Modify
E06.14
AO1 output 0: Running frequency
1: Setting frequency
2: Ramp reference frequency
3: Running rotation speed (relative to twice the
motor synchronization rotation speed)
4: Output current
5: Output current
(relative to twice the motor rated current)
6: Output voltage (relative to 1.5 times the rated
)
7: Output power (relative to twice the rated power
of the motor)
9: Output torque (relative to twice the rated torque
of the motor)
10: Analog AI1 input value (implemented through
the analog potentiometer on the keypad for the
0150G/018P and lower models; not available for
the 018G/022P and higher models.)
11: Analog AI2 input value
12: Analog AI3 input value
13: High speed pulse HDI input value
14: MODBUS communication set value 1
15: MODBUS communication set value 2
22: Torque current (relative to triple the motor
rated current)
23: Ramp reference frequency(with sign)
0
○
E06.15
AO2 output
0
○
E06.16
HDO
high-speed
pulse output
selection
0
○
E06.17
Lower limit of
AO1 output
The above function codes define the relative
relationship between the output value and analog
output. When the output value exceeds the range
of set maximum or minimum output, it will count
according to the low-limit or upper-limit output.
When the analog output is current output, 1mA
0.0%
○
E06.18
Corresponding
AO1 output to
the lower limit
0.00V
○
E06.19 Upper limit of
100.0%
○