added on the output side of the VFD. If the distance between the VFD and motor ranges from 50 m
to 100 m, select the reactor according to the following table. If the distance is longer than 100 m,
contact INVT's technical support. The mapping between VFD models and reactors is as follows:
VFD model
Input reactor
DC reactor
Output reactor
0R7G-4
ACL2-1R5-4
/
OCL2-1R5-4
1R5G-4
ACL2-1R5-4
/
OCL2-1R5-4
2R2G-4
ACL2-2R2-4
/
OCL2-2R2-4
004G/5R5P-4
ACL2-004-4
/
OCL2-004-4
5R5G/7R5P-4
ACL2-5R5-4
/
OCL2-5R5-4
7R5G/011P-4
ACL2-7R5-4
/
OCL2-7R5-4
011G/015P-4
ACL2-011-4
/
OCL2-011-4
015G/018P-4
ACL2-015-4
/
OCL2-015-4
018G/022P-4
ACL2-018-4
/
OCL2-018-4
022G/030P-4
ACL2-022-4
/
OCL2-022-4
030G/037P-4
ACL2-037-4
/
OCL2-037-4
037G/045P-4
ACL2-037-4
DCL2-037-4
OCL2-037-4
045G/055P-4
ACL2-045-4
DCL2-045-4
OCL2-045-4
055G/075P-4
ACL2-055-4
DCL2-055-4
OCL2-055-4
075G/090P-4
ACL2-075-4
DCL2-075-4
OCL2-075-4
090G/110P-4
ACL2-110-4
DCL2-090-4
OCL2-110-4
110G/132P-4
ACL2-110-4
DCL2-132-4
OCL2-110-4
132G/160P-4
ACL2-160-4
DCL2-132-4
OCL2-160-4
160G/185P-4
ACL2-160-4
DCL2-160-4
OCL2-200-4
185G/200P-4
ACL2-200-4
DCL2-220-4
OCL2-200-4
200G/220P-4
ACL2-200-4
DCL2-220-4
OCL2-200-4
220G/250P-4
ACL2-280-4
DCL2-280-4
OCL2-280-4
250G/280P-4
ACL2-280-4
DCL2-280-4
OCL2-280-4
280G/315P-4
ACL2-280-4
DCL2-280-4
OCL2-280-4
315G/355P-4
ACL2-350-4
DCL2-315-4
OCL2-350-4
355G/400P-4
Standard
DCL2-400-4
OCL2-350-4
400G-4
Standard
DCL2-400-4
OCL2-400-4
450G-4
Standard
DCL2-500-4
OCL2-500-4
500G-4
Standard
DCL2-500-4
OCL2-500-4
Note:
1.
The rated derate voltage of the input reactor is 2%±15%.
2.
The power factor of the input side is above 90% after adding DC reactor.
3.
The rated derate voltage of the output reactor is 1%±15%.
4.
The preceding optional parts are externally connected. If the 220G/250P
–315G/355P models