fault), will r
Function Parameters
88
Function
code
Name
Description
Default
value
Modify
BIT5
BIT4 10
00
01
10
11
BIT7
BIT6 11
00
01
10
11
BIT9
BIT8 12
00
01
10
11
BIT11 BIT10 13
00
01
10
11
BIT13 BIT12 14
00
01
10
11
BIT15 BIT14 15
00
01
10
11
After the users select the corresponding
ACC/DEC time, the combined 16 binary bits will
change into decimal bit, and then set the
corresponding function codes.
Setting range: 0x0000
–0xFFFF
E10.36
PLC restart
0: Restart from the first step; stop during running
(cause by the stop command, fault or power loss),
run from the first step after restart.
1: Continue to run from the stop frequency; stop
during running (cause by stop command and
ecord the running time
automatically, enter into the step after restart and
keep the remaining running at the setting
frequency.
0
◎
E10.37
Multi-step time
unit
0: Seconds; the running time of all steps is
counted by second
1: Minutes; the running time of all steps is counted
by minute
0
◎
E11 Group Protective parameters
E11.00
Phase loss
protection
0x00
–0x11
LED ones:
0: Input phase loss protection disable
1: Input phase loss protection enable
LED tens:
0: Output phase loss protection disable
1: Output phase loss protection enable
LED hundreds:
0: Input phase loss hardware protection disable
1: Input phase loss hardware protection enable
111
○
E11.01
Sudden power
loss frequency
decrease
0: Disable
1: Enable
0
○
E11.02
Frequency
decrease ratio
Setting range: 0.00Hz/s
–E00.03 (max. frequency)
After the power loss of the grid, the bus voltage
10.00
Hz/s
○