Function Parameters
58
Function
code
Name
Description
Default
value
Modify
E05.08
S8 terminal
function
selection
36: Shift the command to the keypad
37: Shift the command to the terminals
38: Shift the command to the communication
39: Pre-exciting command
40: Clear the power consumption
41: Keep the power consumption
61: PID pole switching
When the terminal acts as acceleration/
deceleration time selection function, it is required
to select four groups of acceleration/deceleration
time via state combination of these two terminal
(while terminal 1 choose 21, terminal 2 choose 22)
Terminal1
(21)
Terminal2
(22)
ACC/DEC time
selection
Parameters
OFF
OFF
ACC/DEC time 1
ON
OFF
ACC/DEC time 2
OFF
ON
ACC/DEC time 3
ON
ON
ACC/DEC time 4
0
◎
E05.09
HDI terminal
function
selection
0
◎
E05.10
Polarity
selection of the
input terminals
The function code is used to set the polarity of the
input terminals.
Set the bit to 0, the input terminal is anode.
Set the bit to 1, the input terminal is cathode.
BIT0
BIT1
BIT2
BIT3
BIT4
S1
S2
S3
S4
S5
BIT5
BIT6
BIT7
BIT8
S6
S7
S8
HDI
The setting range: 0x000
–0x1FF
0x000
○
E05.11
ON-OFF filter
time
Set the sample filter time of S1
–S8 and HDI
terminals. If the interference is strong, increase the
parameter to avoid the disoperation.
0.000
–1.000s
0.010s
○
E05.12
Virtual
terminals
setting
0x000
–0x1FF(0: Disabled, 1: Enabled )
BIT0: S1
virtual terminal
BIT1: S2
virtual terminal
BIT2: S3
virtual terminal
BIT3: S4
virtual terminal
BIT4: S5
virtual terminal
BIT5: S6
virtual terminal
BIT6: S7
virtual terminal
BIT7: S8
virtual terminal
BIT8: HDI
virtual terminal
Note:
After a virtual terminal is enabled, the
0x000
◎