Item
Data
Remarks
User-defined alarm ID of
extended digital parameter 1: 11
When the fan is faulty, the MA5616
reports an alarm.
The meanings of the alarm IDs are as
follows:
1: AC voltage; 2: AC switch; 3: battery
voltage; 4: battery fuse; 5: load fuse; 6:
rectifier; 7: DC power; 8: room door; 9:
thief; 10: wiring ; 11: fan; 12: fire; 13:
smoke; 14: power supply; 15: water; 16:
diesel; 17: smell 18: air-condition; 19:
arrester; 20: DC voltage; 21 output
switch; 22: digital user-defined alarm
Extended digital parameter ID: 3 -
Valid level of extended digital
parameter 3: low level
When the low level represents the valid
level, the device does not report an
alarm in the case of low level.
Name of extended digital
parameter 3: SPD
It is a user-defined digital parameter and
is set according to the actual
requirements. The monitoring digital
parameter of the SPD status sensor is set
to monitor the SPD status.
User-defined alarm ID of
extended digital parameter 3: 19
When the lightning arrester is faulty, the
MA5616 reports an alarm.
huawei(config)#
emu add 2 POWER4830 0 4 RS485 POWER4830
huawei(config)#
interface emu 2
huawei(config-if-power4830-2)#
display power system parameter
EMU ID: 2 Power system information
----------------------------------------------------------------------------
Charge control state: Automatic control
Equalizing voltage : 56.50V Floating voltage : 53.50V
Charge Lmt quotiety : 0.15 Equalizing time : 60 days
Battery number : 1 Battery 0 capacity : 65 AH
battery temperature test upper : 80C battery temperature test lower: -20C
temperature redeem quotiety : 80mV
battery temperature alarm upper: 50C battery temperature alarm lower: 0C
Battery off permit : Permit Battery off voltage : 43.00V
AC over alarm volt : 280V AC lack alarm voltage : 180V
DC over alarm volt : 58 V DC lack alarm voltage : 45 V
Power module number : 2
module 0 address: 1 module 0 switch state : On
module 1 address: 2 module 1 switch state : On
Battery high-temperature-off permit : Forbid
Battery high-temperature-off temperature: 53 C
----------------------------------------------------------------------------
huawei(config-if-power4830-2)#
display power environment parameter
EMU ID: 2 power environment configration parameter
------------------------------------------------------------------------------
AnalogID Name AlmUpper AlmLower TestUpper TestLower Unit type
0 Temperature 50 0 80 -20 C Current
1 Humidity 80 10 100 0 %R.H. Current