NOTE
Before adding a user-defined analog or digital monitoring parameter, make sure that the port corresponding
to this analog or digital monitoring parameter is properly connected with an environment monitoring cable.
Procedure
Step 1
Add the EPS30-4815AF, namely, Power4830.
Run the
emu add
command to add the Power4830.
Step 2
In the environment monitoring configuration mode, run the
display power system
parameter
command to query the default configuration.
Step 3
Configure the parameters of the lead battery.
Run the
power battery parameter
command to configure battery parameters, including battery
management parameters, charging parameters and battery set power-off parameters, and battery
high-temperature power-off parameters. You can also use the default settings.
Step 4
Configure the parameter of the rectifier unit.
Run the
power module-num
command to configure the parameter of the rectifier unit.
Step 5
Configure the environment parameters for power supply monitoring.
Run the
power environment
command to configure the upper and lower alarm thresholds and
measurement thresholds of temperature or humidity for power monitoring. In this manner, the
power module generates alarms when it works in a condition that does not meet the present
requirements.
Step 6
Configure the external extended digital parameter for power supply monitoring.
Run the
power outside_digital
command to configure the external extended digital parameter
for power supply monitoring.
Step 7
Query configuration parameters and environment parameters of the power system.
Run the
display power system parameter
command to query configuration parameters of the
power monitoring unit.
Step 8
Run the
display power alarm
command to query the alarm. Ensure that no alarm (except the
door status alarm) for the monitoring parameter is generated.
Step 9
Save the data.
Run the
quit
command to quit the Power4830 mode, and then run the
save
command to save
the data.
----End
Result
After the configuration, the EPS30-4815AF works in the normal state and monitors parameters
set on the MA5616. When a monitored parameter is abnormal, the MA5616 reports an alarm.
Example
provides the data plan for configuring the power monitoring through the
EPS30-4815AF.