Example
shows the parameter plan for configuring the H831VESC.
Table 3-23
Data plan for configuring the H831VESC
Item
Data
Remarks
Digital
parameters
Digital parameter ID: 0
In the F01S50 and F01S100 cabinets, digital
parameter 0 is used to monitor the
temperature. In the F01E50 cabinet, digital
parameter 0 does not take effect.
Valid level of digital
parameter 0: low level
When the low level represents the valid level,
the MA5616 does not report an alarm in the
case of low level.
Name of digital parameter 0:
Temperature
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the temperature sensor is set to
monitor the temperature.
User-defined alarm ID of
digital parameter 0: 5
When the temperature in the cabinet is
between 67°C and 73°C, the MA5616 reports
an alarm.
The meanings of the alarm IDs are as follows:
0: smoke ; 1: door; 2: arrester; 3: wiring; 4:
the AC power is off; 5: digital user-defined
alarm
Digital parameter ID: 1
In the F01S50, F01S100, and F01E50
cabinets, digital parameter 1 is used to
monitor door status.
Valid level of digital
parameter 1: high level
When the high level represents the valid level,
the MA5616 does not report an alarm in the
case of high level.
Name of digital parameter 1:
Door
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the door sensor is set to monitor
the door status.
User-defined alarm ID of
digital parameter 1: 1
When the cabinet door is open, the MA5616
reports an alarm.
Digital parameter ID: 2
In the F01S50, F01S100, and F01E50
cabinets, digital parameter 2 is used to
monitor the lightning arrester.
Valid level of digital
parameter 2: low level
When the low level represents the valid level,
the MA5616 does not report an alarm in the
case of low level.