iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
239
Step 7
Click
Connection Test
to start the connection test.
Step 8
After the connection test is successful, click
in the toolbar to save the device
information.
----End
6.4.7 Adding a RPDU
6.4.7.1 Setting Monitoring Parameters for HPXPDU2000-16-3PH-24-6-M1
Prerequisites
You have obtained the device address planned for the PDU2000.
The PDU2000 is connected to the collector, and digits are displayed on the LCD.
You have obtained the collector IP address and login user name and password.
A PC with an IP address in the same network segment as the collector has been prepared
and connected to the collector over a switch.
Context
Before connecting the PDU2000 to the NetEco, set its device address and then modify the
port parameters for the collector connecting to the PDU2000 to ensure that the values of
BaudRate
,
DataBit
,
StopBit,
and
Parity
on it are consistent with those for the collector port.
Procedure
Step 1
Press
MENU
on the PDU2000 display panel.
Step 2
Press
UP
until
is displayed and
ADD
blinks.
Step 3
Press
MENU
,
is displayed, and
01
blinks. The current device address is 01.
Step 4
Press
UP
or
DOWN
to select the device address value.
Step 5
Press
MENU
to confirm the setting.
If
is displayed, the setting succeeds.
If
is displayed, the setting fails. Reset the parameter.
The PDU2000
BaudRate
,
DataBit
,
StopBit
, and
Parity
cannot be set on the WebUI. Their values are
9600
,
8
,
1
, and
None
respectively.
Step 6
Press
Button
.
is displayed. Then press
MENU
to exit.
Step 7
Set RS485 port parameters for the collector based on the values of
BaudRate
,
DataBit
,
StopBit
, and
Parity
of the device. For ECC settings, see