iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
233
Step 7
Click
Connection Test
to start the connection test.
Step 8
After the connection test is successful, click
in the toolbar to save the device
information.
----End
6.4.5 Adding a UPS
6.4.5.1 Setting Monitoring Parameters for a UPS2000
Prerequisites
You have obtained the IP address and user name and password for logging in to the
collector.
A PC with an IP address in the same network segment as the collector has been prepared
and connected to the collector over a switch.
Context
Before connecting the UPS2000 to the NetEco, set monitoring parameters on the UPS2000.
Then, modify the port parameters for the collector connecting to the UPS2000 to ensure that
the values of
BaudRate
,
DataBit
,
StopBit
, and
Parity
on the UPS2000 are consistent with
those for the collector port.
Procedure
Step 1
Set the UPS2000 device address using the DIP switch S2 on the optional Modbus card.
Toggles 1 to 8 of DIP switch S2 specify the device address in binary mode.
ON
indicates
0
,
and
OFF
indicates
1
shows an example of the address settings.
Table 6-40
Mapping between device addresses and Modbus card DIP switch settings
Device
Addre
ss
Toggle
Switch
1
Toggle
Switch
2
Toggle
Switch
3
Toggle
Switch
4
Toggle
Switch
5
Toggle
Switch
6
Toggle
Switch
7
Toggle
Switch
8
1
OFF
ON
ON
ON
ON
ON
ON
ON
2
ON
OFF
ON
ON
ON
ON
ON
ON
3
OFF
OFF
ON
ON
ON
ON
ON
ON
4
ON
ON
OFF
ON
ON
ON
ON
ON
Step 2
Set RS485 port parameters for the collector based on the values of
BaudRate
,
DataBit
,
StopBit
, and
Parity
of the device. For ECC collector settings, see
Parameters for the ECC500 V6 Collector
For the UPS2000, the default values of
BaudRate
,
DataBit
,
StopBit
, and
Parity
are
9600
,
8
,
1
, and
None
, respectively. If the parameters are changed, the actual parameter values prevail.