iManager NetEco 6000
Device Installation and Commissioning Guide
8 FAQ
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
303
8.6 How Do I Change the NetEco IP Address?
Prerequisites
You have logged in to the PowerEcho client using a browser.
You have the operation rights of the ECC800 WebUI, ECC500 WebUI, and UPS2000–G.
Procedure
Step 1
Change the NetEco IP address.
1.
In the browser address bar, enter https://IP address of the NetEco server:32804/, enter the
User Name
and
Password
, and press
Enter
to access the PowerEcho client.
The default user name for the PowerEcho is
admin
and the default password is
Changeme_123
.
2.
After choose
NetEco Maintenance
from the main menu, then choose Server
IP
Address
in the navigation tree on the left side.
3.
Select
Change NetEco/Server IP Address
in
Select
, select the network management IP
address you want to modify in
Current IP Address
.
4.
Enter the new
IP address
,
subnet mask
, and
gateway
for New IP Address, New Subnet
Mask, and New Gateway respectively.
5.
Click
Confirm
.
6.
Choose
Start/Stop NetEco
on the left, click
Start
, type the
Password for PowerEcho
,
and click
Confirm
. Click
Confirm
in the displayed dialog box to start the NetEco
services.
After changing the server IP, please wait for at least 5 minutes and use the new IP address to log in to the
PowerEcho to start NetEco services.
Step 2
Update the NetEco IP address on the ECC800 WebUI.
1.
Log in to the ECC800 WebUI.
Table 8-2
NetEco parameters
Path
Parameter
Default
Value
Setting Value
System
Settings
>
NMS
Application
>
NetEco
>
Communicati
on
Parameters
Server IP
192.168.0.1
1
IP address of the primary NetEco server
NOTE
The NetEco IP address and the ECC800 IP
address must be configured in the same
network to ensure normal connection
between the NetEco and the ECC800.
Port number
31220
31220
Link to the
monitoring IP
address
WAN_1
WAN_1
Step 3
Update the trap target IP address on the ECC500 WebUI.