iManager NetEco 6000
Device Installation and Commissioning Guide
8 FAQ
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
304
1.
Log in to the WebUI of the ECC500 V6 collector.
2.
Choose
System Settings
>
SNMP Settings
.
3.
In the
SNMP Trap
area, select the line where the value of
Trap Target Address
is the
same as the NetEco IP address before change, and click
Delete
.
4.
Set
Trap Target Address
and
Trap Port
and select
SNMP Version
. Set
Trap Target
Address
to the NetEco server IP address and set
Trap Port
to the user-defined port. The
default value of
Trap Port
is 162.
5.
Select
SNMPv3
for
SNMP Version
and a user name for SNMPv3.
6.
After you set the parameters, click
Confirm
and then click
Submit
.
Figure 8-8
Setting SNMPv3 parameters
Step 4
Change the UPS2000-G SNMP trap parameters.
1.
Log in to the UPS2000-G WebUI.
2.
Click
Configure
.
3.
In the
SNMP Trap
area, select the line where the value of
NMS addr
is the same as the
NetEco IP address before change in the
No.
column, and click
Delete
.
4.
Enter the NetEco server IP address in
NMS addr
, set
Permission
to
Write
, write
162
in
Trap port
, and click
Add
.
Figure 8-9
Setting SNMP parameters_01