iManager NetEco 6000
Device Installation and Commissioning Guide
3 Installing Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
32
3.6.7 Installing the Location-type Water Sensor
Context
The location-type water sensor is installed on a 35 mm DIN guide rail and can be
installed on the wall around the detected area.
Install water detection cables surrounding the water leakage area.
To avoid damaging the water sensor, do not unpack it until right before installation.
Procedure
Step 1
Fix a proper length of DIN guide rail to the wall around the detected area.
Step 2
Unpack the location-type water sensor, buckle the module to the DIN guide rail, and ensure
that the latch faces upwards during installation.
The water leakage locator should be installed within 1200 meters of the control host.
The installation height must not exceed 1.5 m. Ensure that the water detection rope is no higher than
the ground.
Hand-write the address in the address blank area.
Figure 3-26
Installation diagram
(1) Latch
(2) DIN guide track
Touch grounded devices or pipes to eliminate ESD before taking the location-type water sensor
module.
Place it gently. Protect it against mechanical impact and collision. Keep it dry.