iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
133
6.3 Scenarios for Connecting the LAN Switch
6.3.1 Adding CIM01C2 Collector(LAN Switch)
6.3.1.1 Setting Parameters on the CIM WebUI
Prerequisites
Operating system: Windows XP or later
Browser: Internet Explorer 9 or later, FireFox 43 or later, and Chrome 41 or later
The IP addresses, subnet masks, and gateways for the PC and CIM are in the same
network segment.
The default settings of the IP address, subnet mask, and gateway are as follows:
IP address: 192.168.0.10
Subnet mask: 255.255.255.0
Gateway: 192.168.0.1
Context
The parallel CIM communication is used to synchronize the analog parameters and
configuration parameters of each CIM system. It can also be used to coordinate the
measurement of internal resistance so that only one BIM is measuring the internal resistance
at one time.
Procedure
Step 1
Connect a straight-through cable from the PC network port to the Ethernet port on the switch.
Step 2
Open Internet Explorer, and choose
Tools
>
Internet Options
.
Step 3
Select the
Advanced
tab, check that
Use TLS 1.1
and
Use TLS 1.2
are selected, and then
click
OK
.