6.4.2.1.2 Setting Smoke Sensor and Water Leakage Sensor Parameters on the ECC
After connecting a smoke sensor or water leakage sensor to the AI/DI port of an ECC500 V6
collector, you need to set smoke sensor or water leakage sensor parameters on the web user
interface (WebUI) of the collector.
Prerequisites
You have obtained the IP address, and login user name and password for the ECC500 V6
collector.
A PC with an IP address in the same network segment as the ECC500 V6 collector is
prepared, and the PC has been connected to the ECC500 V6 collector over a switch.
Context
This section describes how to set smoke sensor or water leakage sensor monitoring
parameters when a smoke sensor or water leakage sensor is connected to the AI/DI_1
port of the MUE05A4 card of an ECC500 V6 collector. Set the parameters based on the
actual port connected to the smoke sensor or water leakage sensor onsite.
A smoke sensor or water leakage sensor is a self-identification device. After a smoke
sensor or water leakage sensor is connected to the AI/DI port of an ECC500 V6 collector,
the sensor type is automatically identified and you do not need to manually set
AI/DI_1
Sensor Type
on the WebUI.
Procedure
Step 1
Log in to the WebUI of the ECC500 V6 collector.
Step 2
Choose
Monitoring
>
MUE05A Expansion Card
>
MUE05A4
>
Running Parameter
>
AI/DI_1 Port Settings
.
Step 3
Select
Enable
for
AI/DI_1 Sensor
.
Step 4
Click
Submit
, as shown in
Figure 6-55
Setting port enabling of a dry contact