6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
231
Table 6-38
Parameter description
Parameter
Description
Communication address
1–255
Indicates the actual address for the
NetCol5000. The devices with the same
address cannot connect to the same port.
When creating a NetCol5000 on the
NetEco, set
Device address
to the same
value.
Baud Rate
9600, 19200
Indicates the baud rate. The default baud
rate is 9600. Set
BaudRate
for the collector
port to the same value.
The NetCol5000
DataBit
,
StopBit
, and
Parity
cannot be set on the WebUI. Their default
values are
8
,
1
, and
None
respectively.
Step 5
Set RS485 port parameters for the collector based on the value of
BaudRate
,
DataBit
,
StopBit
, and
Parity
of the device. For ECC collector settings, see
Parameters for the ECC500 V6 Collector
----End
6.4.4.2 Creating a Smart Cooling Product on the NetEco
Prerequisites
You have logged in to the NetEco client.
You have the operation rights for
Data Center Planning
.
You have created a management domain for the device to be added on the
Data Center
Planning
page.
Procedure
Step 1
Choose
Configuration
>
Configuration Management
>
Data Center Planning
from the
main menu. The
Data Center Planning
window is displayed.
Step 2
Select the management domain to add a device.
Step 3
In the lower-left corner of the page, click the
Device
tab.
Step 4
Click the drop-down list box in
Type
and select
Air Conditioner
.
Step 5
Select the device to be added and drag its icon to the management domain.
To delete a device, click the device and choose
Delete
under
.
Step 6
Specify parameters shown in
in the right pane based on the following table. The
NetCol5000 smart cooling product complying with the MODBUS-RTU protocol is used as an
example.