6.4.1.4 Setting RS485 Parameters for the ECC500 V6 Collector
Prerequisites
You have obtained the IP address, login user name, and password for the ECC500 V6
collector.
A PC with an IP address in the same network segment as the ECC500 V6 collector is
prepared, and the PC has been connected to the ECC500 V6 collector over a switch.
Context
To ensure the normal connection between the ECC500 V6 collector and devices, properly set
the RS485 parameters for the ECC500 V6 collector, such as
BaudRate
,
DataBit
,
StopBit
and
Parity
. Ensure these parameters stay consistent with those of the devices.
This topic describes how to set RS485 port parameters for the COM1 port on the MUS02A
card of the ECC500 V6 collector.
Procedure
Step 1
Set RS485 port parameters on the WebUI of the ECC500 V6 collector.
1.
Use a PC, enter https://
XX.XX.XX.XX
in the address bar to log in to the WebUI of the
ECC500 V6 collector.
XX.XX.XX.XX
indicates the IP address of the collector.
To ensure the security of data transmission, the NetEco transmits data after encrypting it over the
Secure Sockets Layer (SSL).
2.
Choose
Monitoring
>
MUS02A3
>
Running Parameter
>
COM1 Port Settings
.
3.
From the drop-down list, choose
COM1 Baud Rate
,
COM1 Data Bit
,
COM1 Stop Bit
,
COM1 Parity
, and
COM1 TimeOut
as shown in
, click
Submit
.
When
COM1 Data Bit
is set to 7, set
COM1 Parity
to
Odd
or
Even
.
The value range of
COM1 TimeOut
is 200–10,000 ms.
Figure 6-50
Setting RS485 port parameters
Step 2
(Optional) Configure the slots on the ECC500 V6 collector.