iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
157
6.3.3 Adding a Smart Cooling Product
6.3.3.1 Setting Monitoring Parameters for the Smart Cooling Product
The method of setting monitoring parameters for NetCol5000C-65kW&80kW,
NetCol5000-A035/A042/C025/C030 are the same.
Prerequisites
You have obtained the IP address, subnet mask, and default gateway information planned
for the NetCol.
The NetCol is powered on.
Context
NetCol5000C-65kW&80kW, NetCol5000-A035/A042/C025/C030 smart cooling products
support MODBUS-TCP, MODBUS-RTU, and SNMP protocols. When
NetCol5000C-65kW&80kW,NetCol5000-A042/C025/C030 smart cooling products use
MODBUS-TCP connection, refer to this section for configuration details.
This section uses NetCol5000-A035_V100R002C00 as an example.
Procedure
Step 1
Tap
Settings
on the NetCol5000-A035_V100R002C00 home screen.
Step 2
Enter the administrator user name and password and tap
on the screen.
The preset user name and password for the NetCol5000-A035_V100R002C00 are respectively
Admin
and
000001
. To ensure the access security, change the password upon first login.
Step 3
Choose
Comm Settings
>
Modbus Settings
.
Step 4
Set monitoring parameters.
Table 6-10
Parameter description 1
Parameter
Setting