iManager NetEco 6000
Device Installation and Commissioning Guide
7 Device Maintenance
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
264
8.
Install the removed Micro SD and SIM card in the corresponding slot of the new
ECC800 main control module.
Figure 7-4
Installing the Micro SD and SIM cards
9.
Install the spare ECC800 main control module in the ECC800 subrack and tighten the
screws on both sides of the ECC800 main control module.
10.
Connect the communications cable, WiFi module, and antenna to the ECC800 main
control module.
11.
Use the default user name and password to log in to the ECC WebUI.
12.
(Optional) Choose
System Settings
>
SNMP Settings
, and fill out the recorded
information about areas
SNMPv3
and
SNMP Trap
.
13.
(Optional) Choose
System Settings
>
Monitor Module IP
to fill out the recorded IP
address.
14.
Import the backup configuration file or set parameters for the devices that connect to the
ECC800 to ensure normal communication.
15.
Delete the old ECC800 collector on the NetEco. Create a newly-connected ECC800
collector.
7.2.4 Replacing the independent deployment AI/DI unit
Prerequisites
The independent deployment AI/DI unit needs to be replaced.
A spare independent deployment AI/DI unit of the same model is available and
functional.
Context
Recommended tools and materials: Phillips screwdriver
Procedure
Step 1
Disconnect power supply from the independent deployment AI/DI unit. Then, remove cables
that connect the independent deployment AI/DI unit, label the cables, and record where the
labeled cables were connected.