6.3.5 Adding a PDU
6.3.5.1 Setting Monitoring Parameters for a PDU8000 (over SNMP)
Prerequisites
You have obtained the IP address planned for the PDU8000.
The PDU8000 is powered on.
Context
Before connecting the PDU8000 to the NetEco, set monitoring parameters, such as the IP
address, subnet mask, and gateway, on the PDU8000.
Procedure
Step 1
Tap
Settings
on the PDU8000 home screen.
Step 2
Enter the PDU8000 password and tap
on the screen.
The preset user name and password for the PDU8000 are respectively
admin
and
000001
. To ensure
access security, change the password upon first login.
Step 3
Tap
Communication
.
1.
Check that
IP address assign
is set to
Manual
.
2.
Set
IP address
,
Subnet mask
, and
Gateway
as planned.
3.
Click
SNMP Configuration
and enter to the screen.
Figure 6-38
SNMP Configuration
4.
In
SNMP Config.
page, set
SNMP Version
to
SNMPv3
, retain
SNMP Port
default
value
161
, and click
Submit
.
5.
Click
Add
under
SNMPv3 User
. Set
User Name
. Set
Auth. protocol
to
SHA
, and
specify
MD5/SHA
and
Confirm Password
. Set
Private protocol
to
AES
, and specify
DES/AES
and
Confirm Password
. After setting the parameters, click
OK
.
6.
In
Trap Config.
page, click
Add
, set
Trap Des. Address
to the IP address of the
NetEco server and set
Trap Port
to
162
. Select
SNMP Version
to
SNMPv3
. After
setting the parameters, click
OK
.